AUTOMATIC DIFFERENTIAL CONDENSATE CONTROLLER – 30-DC SERIES

30-DC Series is an automatic differential condensate controller in forged steel are designed to function on applications where condensate must be lifted from a drain point or in gravity drainage applications where increased velocity will aid in condensate drainage.

When lifting from the drain point, often referred to as siphon drainage, the reduction in pressure that occurs when the condensate is elevated causes a portion of it to flash back into steam.

Ordinary steam traps, unable to differentiate between flash steam and live steam, close and impede drainage. Increased velocity with gravity drainage will aid in drawing the condensate and air to the DC.

This increased velocity is caused by an internal bypass, controlled by a manual metering valve, so the condensate controller will automatically vent the bypass or secondary steam. This steam is then directed to the condensate return line or collected for use in other heat exchangers.

PRODUCT SPECIFICATIONS

Series 21-DC 22-DC 23-DC 24-DC 25-DC 26-DC
Maximum Capacity 1,050 lb/hr
(476 kg/hr)
2,200 lb/hr
(998 kg/hr)
4,400 lb/hr
(2,000 kg/hr)
6,900 lb/hr
(3,130 kg/hr)
11,000 lb/hr
(4,990 kg/hr)
20,000 lb/hr
(9,072 kg/hr)
Maximum Allowable Pressure 250 psig
(17 bar)
250 psig
(17 bar)
250 psig
(17 bar)
250 psig
(17 bar)
250 psig
(17 bar)
250 psig
(17 bar)
Maximum Allowable Temperature 450°F
(232°C)
450°F
(232°C)
450°F
(232°C)
450°F
(232°C)
450°F
(232°C)
450°F
(232°C)
Body Material ASTM A48
Class 30
Cast Iron
ASTM A48
Class 30
Cast Iron
ASTM A48
Class 30
Cast Iron
ASTM A48
Class 30
Cast Iron
ASTM A48
Class 30
Cast Iron
ASTM A48
Class 30
Cast Iron
Maximum Operating Pressure 250 psig
(17 bar)
250 psig
(17 bar)
250 psig
(17 bar)
250 psig
(17 bar)
250 psig
(17 bar)
250 psig
(17 bar)
Connection Type Screwed Screwed Screwed Screwed Screwed Screwed
Connection Size 1/2″ (15 mm) 3/4″ (20 mm) 1″ (25 mm) 1-1/4″ (32 mm) 1-1/2″ (40 mm) 2″ (50 mm)