BIMETALLIC STEAM TRAP FOR SUPERHEAT CONDITIONS – SH-2000 SERIES
BIMETALLIC STEAM TRAP FOR SUPERHEAT CONDITIONS – SH-2000 SERIES
SH-2000 Series Superheat Steam Traps operate by the effect that rising temperature has on the thermostatic bimetallic elements. It adjusts to changing conditions because the curving of the bimetallic elements, caused by increasing temperature, compensates for increasing pressure.
At start-up, the valve is wide open, which allows a large volume of non-condensables and cold condensate to be removed from the system. When the system reaches steam temperature, the elements become sufficiently hot to pull on the trap’s valve stem, closing the valve.
The valve remains closed until the bimetallic elements cool, thus allowing the valve to crack open, venting the condensate and non-condensables, and then close again when steam temperature is reached.
The SH-2000 Series has a sealed, stainless steel body that is lightweight, compact and highly resistant to corrosion. It is adaptable to an Armstrong 360˚ Universal Connector or a Trap Valve Station (TVS). This makes it easy to install and replace, as the trap can be removed while the connector remains in-line. That means savings in labor cost and ultimate flexibility—because inverted bucket, thermostatic, thermostatic wafer, disc, and float and thermostatic steam traps can all be installed on the same connector.
PRODUCT SPECIFICATIONS
Model | SH-2000 |
Capacities To | 4800 lb/hr (2175 kg/hr) |
Maximum Allowable Pressure | 800 psig (28 bar) |
Maximum Allowable Temperature | 800°F 427°C |
Body Material | Stainless Steel |
Maximum Operating Pressure | 400 psig (28 bar) |
Connection Type | 2-Bolt, Screwed, Socketweld, Flanged |
Connection Size | 1/2″ (15 mm) 3/4″ (20 mm) 1″ (25 mm) |
RESOURCES
DATA SHEETS
Bimetallic Steam Trap SH-2000 Data Sheet
SH-2000 Bimetallic Steam Trap Data Sheet
INSTALLATION AND MAINTENANCE
Bimetallic Steam Trap SH-2000, SH-2500, SH-4000, and AB-3000 IOM